CSLB C-20 HVAC ContractorPlanning and LayoutHard

A Manual D duct design must deliver a total system airflow of 1,500 CFM to match the equipment's rated output. A specific bedroom has a calculated heat load of 3,000 Btu/hr out of a whole-house total load of 45,000 Btu/hr. Using the proportional load-based method for branch duct airflow allocation, how much airflow should be routed to this bedroom's branch duct?

  1. A75 CFM
  2. B200 CFM
  3. C100 CFM
  4. D150 CFM
Show answer & explanation

Correct answer: C. 100 CFM

Room CFM = (Room Load ÷ Total Load) × Total System CFM = (3,000 ÷ 45,000) × 1,500 = 0.0667 × 1,500 = 100 CFM.

Why the other options are wrong

  • A. Understates the proportional share by using an incorrect ratio.
  • B. Double the correct value; likely from doubling the load ratio in error.
  • D. Overstates airflow, roughly 50% higher than the correct proportional value.

Proportional Branch CFM Allocation

In Manual D duct design, each room's branch airflow is allocated proportionally to its share of the whole-house heat load relative to total system airflow.

  • Room CFM = (Room Load / Total Load) × Total System CFM
  • Ensures each space receives conditioning matched to its load
  • Prevents over- or under-conditioning individual rooms

Memory trick: Give each room its fair share of the total air pie.