A gas furnace has an input rating of 80,000 Btu/hr and an AFUE rating of 92%. A Manual J calculation shows the home's design heating load is 68,000 Btu/hr. What is the furnace's actual heating output capacity, and is it adequately sized for the load?

  1. A86,960 Btu/hr output; oversized excessively for the load
  2. B73,600 Btu/hr output; adequately sized for the load
  3. C92,000 Btu/hr output; adequately sized but overrated for the load
  4. D68,000 Btu/hr output; exactly matched to the load
Show answer & explanation

Correct answer: B. 73,600 Btu/hr output; adequately sized for the load

Output capacity = Input × AFUE = 80,000 × 0.92 = 73,600 Btu/hr. Since 73,600 Btu/hr exceeds the 68,000 Btu/hr design heating load by a modest margin (about 8%), the furnace is adequately sized without significant oversizing, consistent with Manual S heating equipment selection guidance.

Why the other options are wrong

  • A. 86,960 Btu/hr incorrectly divides instead of multiplying by AFUE.
  • C. 92,000 Btu/hr incorrectly reverses input and output relationship.
  • D. 68,000 Btu/hr ignores the AFUE conversion and just repeats the load value.

AFUE Output Conversion

A furnace's usable heating output is found by multiplying its input Btu/hr rating by its AFUE efficiency percentage; this output is compared to the Manual J heating load for proper sizing.

  • Output = Input × AFUE
  • Output should meet or slightly exceed the design heating load
  • Manual S limits acceptable oversizing to avoid short-cycling

Memory trick: Input times efficiency equals what actually warms the house.