CSLB C-20 HVAC ContractorPlanning and LayoutHard

A duct system is routed entirely through an unconditioned attic, resulting in an estimated 15% loss of delivered cooling capacity due to duct heat gain. If the conditioned space requires 36,000 Btu/hr of delivered cooling, what equipment output capacity should be selected to compensate for this duct loss?

  1. A41,400 Btu/hr
  2. B39,600 Btu/hr
  3. C38,000 Btu/hr
  4. D42,350 Btu/hr
Show answer & explanation

Correct answer: D. 42,350 Btu/hr

To compensate for a 15% delivery loss, the equipment output must satisfy: Output × (1 − 0.15) = 36,000. Solving gives Output = 36,000 ÷ 0.85 ≈ 42,353 Btu/hr, matching the closest option.

Why the other options are wrong

  • A. This adds 15% directly rather than dividing by 0.85.
  • B. This adds 10% instead of correctly dividing by (1 − 0.15).
  • C. This adds only a flat 2,000 Btu/hr rather than dividing by the loss factor.

Duct Loss Compensation

When ducts run through unconditioned spaces, delivered capacity is reduced by heat gain/loss through duct walls; equipment must be sized larger to compensate, calculated as required load ÷ (1 − loss fraction).

  • Attic ducts commonly lose 10-25% of capacity without proper insulation
  • Formula: Equipment Output = Delivered Load ÷ (1 − loss %)
  • Properly insulating/sealing ducts reduces this compensation need

Memory trick: What the attic steals, the equipment must reveal — divide by what remains.

More Planning and Layout questions