CSLB C-10 Electrical ContractorEquipment and InstallationMedium

A 3-phase, 4-wire feeder supplies a panelboard with a continuous lighting load of 150 amperes and a non-continuous receptacle load of 40 amperes. What is the minimum required ampacity for the feeder conductors before any temperature correction or adjustment factors?

  1. A190 amperes
  2. B150 amperes
  3. C227.5 amperes
  4. D187.5 amperes
Show answer & explanation

Correct answer: C. 227.5 amperes

Per NEC 215.2 and 210.19(A), continuous loads must be multiplied by 125%: 150A x 1.25 = 187.5A. Add the non-continuous load of 40A: 187.5 + 40 = 227.5A minimum feeder ampacity.

Why the other options are wrong

  • A. Incorrectly adds only 100% of continuous load plus a rounded amount.
  • B. Uses only the continuous load, ignoring the non-continuous portion.
  • D. Only accounts for the continuous load at 125%, omitting the 40A non-continuous load.

Continuous + Non-Continuous Feeder Sizing

Feeder conductors must be sized at 125% of continuous loads plus 100% of non-continuous loads.

  • Continuous load = operates 3+ hours
  • 125% factor applies only to continuous portion
  • Add non-continuous load at 100% to get total minimum ampacity

Memory trick: Continuous loads get a 25% cushion; non-continuous loads stay as-is.