CSLB C-10 Electrical ContractorEquipment and InstallationMedium

A single-phase motor has a nameplate FLC of 40 amperes. The installer plans to use an inverse-time circuit breaker for branch-circuit short-circuit and ground-fault protection. Per NEC Table 430.52, what is the maximum standard breaker size permitted without invoking any exception?

  1. A50 amperes
  2. B80 amperes
  3. C100 amperes
  4. D125 amperes
Show answer & explanation

Correct answer: C. 100 amperes

Table 430.52 permits inverse-time circuit breakers sized up to 250% of motor FLC for typical motors. 40A × 2.50 = 100A, which is a standard breaker size, so 100A is the maximum without needing the oversizing exception.

Why the other options are wrong

  • A. 50A is far below the 250% allowance and unnecessarily restrictive.
  • B. 80A corresponds to 200%, which is used for instantaneous-trip breakers, not standard inverse-time breakers.
  • D. 125A exceeds the calculated 100A maximum and would require invoking the 430.52(C)(1) Exception for next standard size up.

Motor Short-Circuit Protection Sizing

NEC Table 430.52 sets maximum percentages of motor FLC for sizing branch-circuit short-circuit and ground-fault protective devices, varying by device type.

  • Inverse-time breaker: max 250% of FLC (typical motors)
  • Non-time delay fuse: max 300% of FLC
  • Instantaneous-trip breaker: max 800% (or higher with exceptions)
  • Exception allows next standard size up if calculated value isn't standard

Memory trick: Inverse-time breakers get two-and-a-half times the current.

More Equipment and Installation questions