CSLB C-10 Electrical ContractorEquipment and InstallationMedium

A dedicated lighting branch circuit supplies a continuous load of 32 amperes for 4+ hours daily. What is the minimum standard overcurrent device size required for this branch circuit conductor?

  1. A45 amperes
  2. B40 amperes
  3. C32 amperes
  4. D35 amperes
Show answer & explanation

Correct answer: B. 40 amperes

Continuous loads require conductors and OCPDs sized at 125% of the continuous load per NEC 210.19(A) and 210.20(A). 32A × 1.25 = 40A, which is a standard breaker size, so a 40A OCPD is the minimum.

Why the other options are wrong

  • A. 45A exceeds the calculated minimum and is not a standard breaker size, making it an unnecessary oversizing.
  • C. 32A equals only 100% of the load; continuous loads require the 125% multiplier.
  • D. 35A is not a standard overcurrent device size and is below the calculated 40A minimum.

Continuous Load Sizing

Continuous loads (operating 3+ hours) require branch-circuit conductors and OCPDs rated at not less than 125% of the continuous load per NEC 210.19/210.20.

  • Continuous = operates 3 hours or more
  • Formula: OCPD/conductor ≥ 1.25 × continuous load
  • Round up to next standard OCPD size if calculated value isn't standard

Memory trick: Continuous loads need a 25% safety cushion.