CSLB C-10 Electrical ContractorEquipment and InstallationMedium

A 3-phase induction motor has a nameplate full-load current (FLC) of 28 amperes and a marked service factor of 1.15. Per NEC 430.32, what is the maximum permitted overload device setting for continuous-duty protection of this motor?

  1. A42 amperes
  2. B28 amperes
  3. C35 amperes
  4. D31.5 amperes
Show answer & explanation

Correct answer: C. 35 amperes

NEC 430.32(A)(1) permits overload protection sized at up to 125% of motor FLC for motors with a service factor of 1.15 or greater. 28A × 1.25 = 35A.

Why the other options are wrong

  • A. 42A corresponds to 150%, which exceeds the overload limit (that percentage applies to short-circuit protection, not overloads).
  • B. 28A is 100% of FLC, not the maximum allowed overload setting.
  • D. 31.5A corresponds to 112.5%, which is not the applicable multiplier here.

Motor Overload Sizing

NEC 430.32 sets maximum overload relay/device settings based on motor service factor or temperature rise to protect against sustained overcurrent.

  • SF ≥1.15 or temp rise ≤40°C: max 125% of FLC
  • All other motors: max 115% of FLC
  • Overload protects windings from long-term overheating, not short circuits

Memory trick: High service factor motors get a bigger 125% cushion.