Journeyman Electrician Exam (NEC)Wiring Methods and MaterialsMedium

A residential electrician is installing a new 200-amp, 120/240-volt single-phase service entrance. The grounding electrode conductor (GEC) will connect to a ground rod. What is the minimum size for the GEC when connected to a ground rod, assuming the service conductors are 3/0 AWG copper?

  1. A8 AWG copper
  2. B6 AWG copper
  3. C4 AWG copper
  4. D2 AWG copper
Show answer & explanation

Correct answer: B. 6 AWG copper

NEC Section 250.66(A) specifies that a grounding electrode conductor connected to a ground rod, pipe, or plate electrode shall not be required to be larger than 6 AWG copper. The size of the service conductor (3/0 AWG) would normally suggest a larger GEC, but the ground rod electrode limits the GEC size to 6 AWG.

Why the other options are wrong

  • A. This is smaller than the minimum required size.
  • C. This is larger than the minimum required size for a ground rod electrode.
  • D. This is larger than the minimum required size for a ground rod electrode.

GEC Sizing (Ground Rod Exception)

The specific minimum size for a grounding electrode conductor when connected to a ground rod, irrespective of the service entrance conductor size.

  • Overrides standard GEC sizing tables.
  • Applies specifically to ground rod, pipe, or plate electrodes.
  • Ensures adequate fault current path to the electrode.

Memory trick: Six gauge copper, for the ground rod's cover.

More Wiring Methods and Materials questions