Journeyman Electrician Exam (NEC)Wiring Methods and MaterialsMedium

A journeyman electrician is installing a new 240-volt, 30-amp circuit for a water heater in a dwelling unit. The circuit will be run through a 1/2-inch EMT conduit. What is the maximum number of 10 AWG THHN copper conductors permitted in this conduit?

  1. A4
  2. B5
  3. C3
  4. D6
Show answer & explanation

Correct answer: B. 5

According to NEC Chapter 9, Table C.1 (for EMT) and referencing 10 AWG THHN conductors, a 1/2-inch EMT conduit is permitted to contain a maximum of 5 such conductors. This ensures proper heat dissipation and ease of pulling.

Why the other options are wrong

  • A. 4 is too few; 1/2-inch EMT can hold more 10 AWG THHN.
  • C. 3 is too few; 1/2-inch EMT can hold more 10 AWG THHN.
  • D. 6 is too many for 1/2-inch EMT with 10 AWG THHN conductors.

Conduit Fill (Specific Conductors)

The maximum number of specific conductor types and sizes permitted within a given conduit trade size, ensuring that the conduit is not overfilled, which could lead to overheating and difficulty in pulling wires.

  • Based on conductor insulation type and size.
  • Found in NEC Chapter 9, Tables C.1 through C.12(A).
  • Prevents overheating and facilitates installation.

Memory trick: Fill the pipe right, don't cram, use the 'C' tables for the count.