Journeyman Electrician Exam (NEC)Wiring Methods and MaterialsMedium

A commercial building requires a new 208-volt, 3-phase, 60-amp feeder circuit to a subpanel. The circuit will be run using 1 AWG THHN copper conductors. What is the maximum number of current-carrying conductors allowed in a 1-inch trade size Rigid Metal Conduit (RMC) before derating factors must be applied?

  1. A4 conductors
  2. B3 conductors
  3. C9 conductors
  4. D5 conductors
Show answer & explanation

Correct answer: B. 3 conductors

According to NEC Table 310.15(C)(1), ampacity adjustment factors must be applied when the number of current-carrying conductors in a raceway or cable exceeds three. Therefore, up to 3 current-carrying conductors can be installed without applying a derating factor.

Why the other options are wrong

  • A. Incorrect. Derating factors apply for 4 to 6 current-carrying conductors (80% adjustment).
  • C. Incorrect. Derating factors apply for 4 or more current-carrying conductors (70% for 7-9 conductors).
  • D. Incorrect. Derating factors apply for 4 or more current-carrying conductors.

Conductor Ampacity Derating (Number of Conductors)

The reduction in a conductor's allowable ampacity when the number of current-carrying conductors in a raceway, cable, or bundle exceeds a specified limit.

  • Caused by heat buildup from adjacent conductors.
  • Governed by NEC Table 310.15(C)(1) (formerly Table 310.15(B)(3)(a)).
  • Applies when more than three current-carrying conductors are present.

Memory trick: Three is Free, More is Less.