Master Electrician Exam (NEC)Services, Feeders, and Branch CircuitsMedium

A residential garage is being built detached from the main dwelling unit. It will be supplied by a 60A feeder from the main house panel. The garage has a grounding electrode system consisting of two ground rods. What is the minimum size required for the grounding electrode conductor (GEC) from the garage subpanel to these ground rods?

  1. A8 AWG copper
  2. B4 AWG copper
  3. C2 AWG copper
  4. D6 AWG copper
Show answer & explanation

Correct answer: D. 6 AWG copper

For a detached building's grounding electrode conductor, if the only electrode is a ground rod (a made electrode), the GEC is not required to be larger than 6 AWG copper, according to NEC 250.66(A). The feeder size does not directly determine the GEC size for ground rods, as 250.66(A) provides a specific maximum.

Why the other options are wrong

  • A. This size is too small for a GEC to a ground rod.
  • B. This size is larger than the minimum required.
  • C. This size is larger than the minimum required.

GEC Sizing (Ground Rod Electrode)

The grounding electrode conductor (GEC) connects the service equipment or a separately derived system to the grounding electrode system.

  • Sizing generally follows NEC Table 250.66 based on the largest ungrounded service or feeder conductor.
  • For made electrodes like ground rods, a specific maximum size of 6 AWG copper applies.
  • This 6 AWG limit applies regardless of the feeder or service conductor size.

Memory trick: Ground rod GEC: always a 6, copper, no bigger.