Master Electrician Exam (NEC)Services, Feeders, and Branch CircuitsEasy

A commercial kitchen is being renovated, and a new 208Y/120V, 3-phase, 4-wire feeder is being installed from the main service panel to a subpanel in the kitchen. The feeder is protected by a 100A overcurrent device. What is the minimum size copper equipment grounding conductor required for this feeder?

  1. A4 AWG copper
  2. B6 AWG copper
  3. C10 AWG copper
  4. D8 AWG copper
Show answer & explanation

Correct answer: D. 8 AWG copper

According to NEC Table 250.122, for a feeder protected by a 100A overcurrent device, the minimum size for a copper equipment grounding conductor is 8 AWG.

Why the other options are wrong

  • A. This size is larger than the minimum required but could be used.
  • B. This size is larger than the minimum required but could be used.
  • C. This size is too small for a 100A overcurrent device, according to NEC Table 250.122.

Feeder Equipment Grounding Conductor Sizing

The equipment grounding conductor (EGC) for a feeder provides a low-impedance path for ground-fault current from equipment to the service disconnecting means.

  • Sized based on the rating of the overcurrent protective device protecting the feeder.
  • Refer to NEC Table 250.122.
  • Ensures proper operation of overcurrent protective devices during a ground fault.

Memory trick: EGC protects by current, not load.

More Services, Feeders, and Branch Circuits questions