Master Electrician Exam (NEC)Services, Feeders, and Branch CircuitsMedium

A circuit for a 3-phase, 480V, 20 HP motor requires a feeder. The motor has a full-load current (FLC) of 27A. The feeder conductors are copper, installed in conduit, and rated for 75°C. What is the minimum required ampacity for the feeder conductors supplying this motor?

  1. A34A
  2. B27A
  3. C41A
  4. D48A
Show answer & explanation

Correct answer: A. 34A

According to NEC 430.22(A), conductors supplying a single motor used in a continuous duty application must have an ampacity of not less than 125% of the motor's FLC. Calculation: 27A (FLC) * 1.25 = 33.75A. The next standard conductor ampacity would be 34A or higher. This ensures the conductors can handle the motor's continuous operating current safely.

Why the other options are wrong

  • B. 27A is the FLC, not the minimum required ampacity for continuous duty, which requires 125% of FLC.
  • C. 41A is higher than required, leading to unnecessary cost.
  • D. 48A is significantly higher than required, leading to unnecessary cost.

Motor Feeder Conductor Sizing

Conductors supplying a single motor used in a continuous duty application must have an ampacity of not less than 125% of the motor's full-load current (FLC), as per NEC 430.22(A).

  • Applies to continuous duty motors.
  • Requires 125% of the motor's FLC.
  • FLC is found in NEC Tables 430.247-430.250.
  • Ensures conductors can handle sustained motor operation.

Memory trick: Motor Wires: Full-load current, plus a safety margin, ensures it's right.

More Services, Feeders, and Branch Circuits questions