Journeyman Electrician Exam (NEC)Services, Feeders, and Branch CircuitsEasy

A client requests the installation of a 120-volt, 20-ampere branch circuit for lighting in a dwelling unit. The circuit conductors are run in EMT conduit. What is the minimum size copper equipment grounding conductor (EGC) required for this circuit, according to NEC 250.122?

  1. ANo. 10 AWG copper
  2. BNo. 8 AWG copper
  3. CNo. 12 AWG copper
  4. DNo. 14 AWG copper
Show answer & explanation

Correct answer: C. No. 12 AWG copper

According to NEC Table 250.122, for a circuit with an overcurrent protective device rating of 20 amperes, the minimum size copper equipment grounding conductor required is No. 12 AWG.

Why the other options are wrong

  • A. No. 10 AWG copper is required for 60-ampere circuits or larger, not a 20-ampere circuit.
  • B. No. 8 AWG copper is required for 100-ampere circuits or larger, not a 20-ampere circuit.
  • D. No. 14 AWG copper is the minimum size for a 15-ampere circuit, not a 20-ampere circuit.

EGC Sizing (Branch Circuit)

The minimum size of an equipment grounding conductor (EGC) for a branch circuit is determined by the rating of the overcurrent protective device (OCPD) for that circuit, as specified in NEC Table 250.122.

  • Size depends on OCPD rating.
  • NEC Table 250.122 is the reference.
  • Ensures proper fault current path.

Memory trick: Grounding Wire: OCPD Dictates Diameter.