A commercial kitchen requires ground-fault protection for equipment (GFPE) on a 480Y/277V, 3-phase, 4-wire service rated at 1200 amperes. According to NEC 230.95(A), what is the maximum setting for the GFP device's instantaneous trip?

  1. A1000 amperes
  2. B1200 amperes
  3. C3000 amperes
  4. D2400 amperes
Show answer & explanation

Correct answer: B. 1200 amperes

NEC 230.95(A) specifies that ground-fault protection of equipment shall be provided for solidly grounded wye services of more than 150 volts to ground but not exceeding 1000 volts phase-to-phase for each service disconnect rated 1000 amperes or more. The maximum setting of the ground-fault protection shall be 1200 amperes.

Why the other options are wrong

  • A. While 1000A is the threshold for requiring GFPE, it is not the maximum setting for the device.
  • C. This value significantly exceeds the NEC requirement and would offer insufficient protection.
  • D. This value significantly exceeds the NEC requirement for ground-fault protection settings.

Ground-Fault Protection of Equipment (GFPE)

GFPE is a system designed to protect equipment and property from damaging ground-fault currents, typically found on larger services, by opening the circuit before extensive damage occurs.

  • Required for 480Y/277V, 3-phase, 4-wire services rated 1000A or more.
  • Maximum setting for the ground-fault device is 1200A.
  • Not intended for personnel protection.

Memory trick: Ground Faults need 'EQ'uipment 'P'rotection, 'E'veryone needs to know the '230.95' rule.