Master Electrician Exam (NEC)Overcurrent ProtectionHard

A new commercial refrigeration unit with a total connected load of 45 amperes (continuous) is being installed. The circuit conductors are rated for 75°C. What is the minimum continuous current rating required for the overcurrent protective device (OCPD), considering NEC 210.20(A) for continuous loads?

  1. A60 amperes
  2. B45 amperes
  3. C50 amperes
  4. D56.25 amperes
Show answer & explanation

Correct answer: A. 60 amperes

According to NEC 210.20(A), the overcurrent device for continuous loads must be sized at 125% of the continuous load. For a 45-ampere continuous load, 45 A * 1.25 = 56.25 A. Since 56.25 A is not a standard overcurrent device size (NEC 240.6), the next higher standard size is permitted, which is 60 amperes.

Why the other options are wrong

  • B. This rating is equal to the continuous load but does not account for the 125% requirement for continuous loads.
  • C. This is a standard size, but it is less than the calculated 56.25A, so it would likely trip prematurely.
  • D. This is the calculated minimum (45A x 1.25). However, it is not a standard overcurrent device size.

Continuous Load OCPD Sizing

For continuous loads (expected to operate for 3 hours or more), the overcurrent protective device (OCPD) must have a rating not less than 125% of the continuous load current.

  • Continuous load is 3 hours or more (NEC 100).
  • OCPD must be sized at 125% of the continuous load (NEC 210.20(A)).
  • Next higher standard OCPD size is permitted if 125% value is not standard.

Memory trick: Continuous loads are a '125%' commitment, so size the 'OCPD' accordingly, then go 'Next'!