Master Electrician Exam (NEC)Overcurrent ProtectionMedium

A newly installed industrial motor has a full-load current (FLA) of 60 amperes. Per NEC, what is the maximum rating for the inverse time circuit breaker used for short-circuit and ground-fault protection if the motor is not a special type and is started across the line?

  1. A150 amperes
  2. B200 amperes
  3. C75 amperes
  4. D175 amperes
Show answer & explanation

Correct answer: D. 175 amperes

NEC Table 430.52 allows an inverse time circuit breaker to be sized up to 250% of the motor's full-load current for short-circuit and ground-fault protection. Therefore, 60 A * 2.50 = 150 A. However, if 150 A is not a standard size, the next higher standard size is permitted if it does not exceed 400% of FLA.

Why the other options are wrong

  • A. This is 250% of the FLA, but 175A is the next standard size available.
  • B. This value exceeds the maximum allowable percentage for an inverse time circuit breaker when the next standard size rule is applied (400% of FLA would be 240A, so 200A is within this, but 175A is the correct next standard size from 150A).
  • C. This value is too low and would likely cause nuisance tripping.

Motor Short-Circuit Protection Sizing

The maximum rating of a motor's short-circuit and ground-fault protective device is determined by the motor's full-load current (FLA) and the type of protective device, as specified in NEC Table 430.52.

  • Inverse time breakers are generally allowed up to 250% of FLA.
  • If the calculated value isn't a standard size, the next higher standard size is permitted.
  • The maximum for inverse time breakers, even with the next size rule, is 400% of FLA.

Memory trick: Motor protection is a 'FLA'shy calculation, always check the 'Tab'le.