Master Electrician Exam (NEC)Overcurrent ProtectionMedium

An electrician is installing a 200-ampere feeder for a commercial building. The feeder protection is provided by a circuit breaker. What is the maximum continuous load permitted on this feeder if the overcurrent protective device is not specifically listed for 100% continuous operation?

  1. A120 amperes
  2. B250 amperes
  3. C200 amperes
  4. D160 amperes
Show answer & explanation

Correct answer: D. 160 amperes

According to NEC 210.20(A) and 215.2(A)(1), the overcurrent device for a continuous load shall be sized at not less than 125% of the continuous load. Conversely, if the OCPD is rated for 200A and not 100% rated, it can only carry 80% of its rating continuously (200A * 0.80 = 160A).

Why the other options are wrong

  • A. This represents 60% of the OCPD rating, which is too low.
  • B. This exceeds the rating of the overcurrent device.
  • C. This would only be permissible if the overcurrent device was specifically listed for 100% continuous operation.

Continuous Load Protection

For continuous loads (operating for 3 hours or more), the overcurrent device must be sized at no less than 125% of the continuous load, or the continuous load must not exceed 80% of the overcurrent device rating, unless the device is 100% rated.

  • Continuous load: 3 hours or more.
  • OCPD must be 125% of continuous load.
  • Continuous load must be 80% of OCPD rating (if not 100% rated).

Memory trick: Continuous loads need 'time' and 'extra' protection, like a 'long' journey.