Master Electrician Exam (NEC)Overcurrent ProtectionMedium

A residential dwelling unit has a 200-ampere service. A new electric range with a nameplate rating of 12 kW (120/240V) is being installed. The branch circuit conductors for the range are 6 AWG copper with THHN insulation. What is the minimum size overcurrent protective device required for the branch circuit supplying this range?

  1. A30 amperes
  2. B40 amperes
  3. C60 amperes
  4. D50 amperes
Show answer & explanation

Correct answer: D. 50 amperes

First, calculate the current: I = P/E = 12,000 W / 240 V = 50 A. According to NEC 210.19(A)(3) and 210.20(A), for household cooking appliances, the branch circuit OCPD must be sized at 100% of the calculated load. Thus, a 50 A OCPD is required. For 6 AWG THHN copper, its ampacity at 90°C is 75 A, which is sufficient. The 60°C column ampacity for 6 AWG is 55 A, also sufficient.

Why the other options are wrong

  • A. This is too low for a 12 kW range (12000W/240V = 50A).
  • B. This is too low for a 12 kW range.
  • C. While 60 amperes would protect the conductors, the question asks for the *minimum* size required for the load.

Electric Range OCPD Sizing

The overcurrent protective device for an individual household electric range branch circuit is sized at 100% of the calculated load, as per NEC 210.19(A)(3) and 210.20(A).

  • Calculate current (I = P/E).
  • OCPD at 100% of calculated load.
  • Conductor ampacity must support the load.

Memory trick: Cooking 'appliances' need 'right-sized' 'power' protection.

More Overcurrent Protection questions