CSLB C-36 Plumbing ContractorRough-in PlumbingHard

A plumbing inspector notes that a relief valve discharge pipe from a water heater is terminated directly into a floor drain. What is the primary reason this installation violates the California Plumbing Code (CPC)?

  1. AThe discharge pipe must be insulated.
  2. BThe discharge pipe must terminate with an air gap.
  3. CThe discharge pipe must be larger than the relief valve outlet.
  4. DThe discharge pipe must be made of copper or galvanized steel.
Show answer & explanation

Correct answer: B. The discharge pipe must terminate with an air gap.

The California Plumbing Code (CPC) mandates that the discharge pipe from a temperature and pressure (T&P) relief valve must terminate with an air gap. This prevents potential back-siphonage of contaminated water from the drain into the potable water system through the relief valve, protecting the water supply from contamination.

Why the other options are wrong

  • A. Insulation is not a code requirement for relief valve discharge pipes.
  • C. While discharge pipes have minimum sizing requirements, this isn't the primary reason for a violation when terminating directly into a drain.
  • D. The material of the discharge pipe is specified (e.g., CPVC, copper, galvanized steel, polypropylene), but direct termination without an air gap is the more critical violation.

T&P Relief Valve Discharge

The safe and visible termination of the pipe carrying hot water from a water heater's temperature and pressure relief valve, designed to prevent scalding and system overpressure.

  • Prevents building of dangerous pressure/temperature.
  • Must discharge to a safe, visible location.
  • Requires an air gap to prevent cross-connection.

Memory trick: T&P pipe, don't be a dunce, air gap always, all at once.