CSLB C-20 HVAC ContractorCooling and RefrigerationHard

A technician is installing a TXV remote sensing bulb on a 1-1/8 inch OD horizontal suction line (a larger diameter line). Per standard industry practice, where should the bulb be mounted for accurate sensing?

  1. AAt the 12 o'clock position (top of the line)
  2. BAt the 6 o'clock position (bottom of the line)
  3. CAt the 4 or 8 o'clock position, avoiding the oil layer at the bottom and vapor stratification at the top
  4. DOn the liquid line near the condenser outlet
Show answer & explanation

Correct answer: C. At the 4 or 8 o'clock position, avoiding the oil layer at the bottom and vapor stratification at the top

On larger suction lines (typically 7/8 inch OD and above), oil tends to pool at the bottom (6 o'clock) while refrigerant vapor can stratify at the top (12 o'clock), both giving inaccurate temperature readings. The 4 or 8 o'clock position avoids both issues and gives the most accurate bulb temperature sensing. Smaller lines can typically use the 12 o'clock position since stratification is less of a concern.

Why the other options are wrong

  • A. On larger lines, vapor stratification at the top can cause inaccurate readings; 12 o'clock is preferred only on smaller lines.
  • B. Oil pooling at the bottom of larger lines skews temperature readings, making 6 o'clock unreliable.
  • D. The TXV bulb senses the suction line temperature, not the liquid line.

TXV Bulb Placement

The TXV remote sensing bulb must be mounted on the suction line at a position that avoids oil pooling and vapor stratification for accurate superheat control.

  • Small suction lines (under ~7/8 in): mount at 12 o'clock
  • Large suction lines: mount at 4 or 8 o'clock to avoid oil (bottom) and stratification (top)
  • Bulb must be insulated and have good thermal contact with the line

Memory trick: Big pipe? Go to the side (4 or 8), not top or bottom