CSLB C-20 HVAC ContractorVentilation and Air DistributionMedium

A room has a calculated sensible heat gain of 24,000 BTU/hr. The design temperature split (supply air to room air) is 20°F. Using the standard sensible heat formula, how much supply airflow (CFM) is required to offset this load?

  1. A1,440 CFM
  2. B800 CFM
  3. C960 CFM
  4. D1,111 CFM
Show answer & explanation

Correct answer: D. 1,111 CFM

CFM = BTU/hr ÷ (1.08 × ΔT) = 24,000 ÷ (1.08 × 20) = 24,000 ÷ 21.6 ≈ 1,111 CFM. The constant 1.08 accounts for air density and specific heat at standard conditions.

Why the other options are wrong

  • A. This overstates CFM, likely from omitting the 1.08 constant.
  • B. This results from dividing by too large a denominator, understating airflow.
  • C. Close but results from using an incorrect constant instead of 1.08.

Sensible Heat CFM Formula

CFM = BTU/hr ÷ (1.08 × ΔT), used to determine airflow needed to offset a sensible heat load.

  • 1.08 is the standard air density/specific heat constant
  • ΔT is temperature difference between supply and room air
  • Used for both heating and cooling load airflow sizing

Memory trick: BTU over 1.08 times Delta-T gives you the CFM.