CSLB C-20 HVAC ContractorHeating SystemsHard

A confined utility room contains a 100,000 Btu/h furnace and a 40,000 Btu/h water heater. The installer plans to use the single permanent opening method (1 square inch per 3,000 Btu/h) with the opening located within 12 inches of the ceiling, connecting directly to the outdoors. What minimum free area is required for this opening?

  1. A23.3 square inches
  2. B46.7 square inches
  3. C33.3 square inches
  4. D70.0 square inches
Show answer & explanation

Correct answer: B. 46.7 square inches

Total input = 100,000 + 40,000 = 140,000 Btu/h. Using the single-opening outdoor-air method requires 1 sq. in. per 3,000 Btu/h: 140,000 ÷ 3,000 = 46.67 sq. in., which rounds up to 47 sq. in. of free area for the single opening.

Why the other options are wrong

  • A. 23.3 sq in would result from using the two-opening 1-in-per-4,000-Btu/h method incorrectly on total input, not the single-opening method.
  • C. 33.3 sq in reflects using only the water heater load, an incomplete calculation.
  • D. 70 sq in would apply if using a 1:2,000 ratio, which is not the standard single-opening rule.

Single Permanent Opening Method

A combustion air method requiring one opening within 12 inches of the ceiling, sized at 1 square inch of free area per 3,000 Btu/h of total appliance input, connecting directly or via duct to outdoor air.

  • Total input of all appliances in confined space must be combined
  • Opening must be within 12 in. of ceiling
  • Differs from the two-opening method (1 sq in per 4,000 Btu/h from outdoors)

Memory trick: Single opening: divide total Btu by 3,000.