CSLB C-20 HVAC ContractorHeating SystemsHard

A heat pump delivers 22,000 Btu/h of heating output while drawing 2,800 watts of electrical input. What is the approximate COP (coefficient of performance) of this unit?

  1. A3.1
  2. B4.5
  3. C1.8
  4. D2.3
Show answer & explanation

Correct answer: D. 2.3

Convert electrical input to Btu/h: 2,800 W × 3.412 Btu/Wh ≈ 9,554 Btu/h. COP = heat output ÷ electrical input in equivalent units = 22,000 ÷ 9,554 ≈ 2.3. This means the heat pump delivers about 2.3 times more heat energy than the electrical energy it consumes.

Why the other options are wrong

  • A. 3.1 would require significantly higher output or lower wattage than given.
  • B. 4.5 is unrealistically high for typical residential heat pump performance at this input.
  • C. 1.8 would result from underestimating the output or overestimating the wattage conversion.

Coefficient of Performance (COP)

A ratio comparing a heat pump's heating output to its electrical energy input, both expressed in the same units, indicating heating efficiency.

  • Formula: COP = heat output (Btu/h) ÷ (watts × 3.412)
  • Typical residential heat pump COP ranges from 2.0 to 4.0
  • Higher COP means more efficient heat delivery per unit of electricity

Memory trick: Watts times 3.412 gives Btu; divide output by that.