CSLB C-20 HVAC ContractorCooling and RefrigerationHard

A technician suspects a restricted liquid line filter drier on an operating system. Which field test would best confirm this diagnosis?

  1. AMeasuring a significant temperature drop (often with visible frost) across the filter drier, with the outlet noticeably colder than the inlet
  2. BChecking for bubbles at the compressor discharge port
  3. CMeasuring identical temperatures on the inlet and outlet fittings of the filter drier
  4. DMeasuring superheat only at the evaporator outlet
Show answer & explanation

Correct answer: A. Measuring a significant temperature drop (often with visible frost) across the filter drier, with the outlet noticeably colder than the inlet

A restriction in the filter drier causes a pressure drop across it, which lowers the saturation temperature of the refrigerant downstream, producing a measurable (sometimes frost-visible) temperature drop between the inlet and outlet fittings — a classic sign of a clogged drier.

Why the other options are wrong

  • B. Discharge bubbles are not a valid or accessible test point for this diagnosis.
  • C. Equal temperatures indicate free flow with no restriction, ruling out the suspected fault.
  • D. Evaporator superheat alone doesn't isolate the restriction to the filter drier specifically.

Restricted Filter Drier Diagnosis

A restricted filter drier causes a pressure drop that lowers refrigerant saturation temperature downstream, producing a measurable temperature drop (often with frost) across the component.

  • Restriction causes pressure drop = temperature drop across component
  • Frost may form at/after the restriction
  • Confirmed by comparing inlet vs outlet temperatures with a thermometer

Memory trick: A cold spot after the drier means it's clogged.

More Cooling and Refrigeration questions