CSLB C-20 HVAC ContractorPlanning and LayoutMedium

A branch duct supplies air to a bedroom register in an occupied living space. To avoid objectionable air noise, Manual D recommends the branch duct velocity not exceed approximately which of the following?

  1. A1,200 feet per minute
  2. B900 feet per minute
  3. C600 feet per minute
  4. D300 feet per minute
Show answer & explanation

Correct answer: C. 600 feet per minute

Manual D recommends limiting branch duct velocities in occupied spaces to around 600 fpm to prevent noticeable air noise at registers, while trunk ducts in occupied spaces can run slightly higher (700-900 fpm) since they are farther from occupants.

Why the other options are wrong

  • A. Too high; this velocity would create excessive register noise.
  • B. This is closer to the acceptable trunk duct velocity, not branch duct.
  • D. Unnecessarily conservative and would require oversized ductwork.

Duct Velocity Noise Limits

Manual D recommends maximum air velocities in occupied spaces to prevent noise: about 600 fpm for branch ducts and 700-900 fpm for trunk ducts.

  • Branch ducts near occupants need lower velocity
  • Trunk ducts can run faster since farther from occupants
  • Excessive velocity causes register whistling/noise

Memory trick: Slow it down near the bed, speed's fine in the trunk instead.