Journeyman Electrician Exam (NEC)Services, Feeders, and Branch CircuitsMedium

A commercial kitchen requires a feeder for a continuous load of 75 amperes and a noncontinuous load of 50 amperes. The feeder conductors are copper, rated 75°C. What is the minimum required rating of the overcurrent protective device (OCPD) for this feeder?

  1. A100 amperes
  2. B150 amperes
  3. C175 amperes
  4. D125 amperes
Show answer & explanation

Correct answer: B. 150 amperes

According to NEC 215.2(A)(1)(a) and 215.3, the feeder OCPD must be sized for 125% of the continuous load plus 100% of the noncontinuous load. Continuous load = 75 A * 1.25 = 93.75 A. Noncontinuous load = 50 A. Total calculated load = 93.75 A + 50 A = 143.75 A. The next standard OCPD size is 150 amperes (NEC 240.6(A)).

Why the other options are wrong

  • A. 100 amperes is too small; it does not account for the 125% factor for the continuous load.
  • C. 175 amperes is larger than the minimum required OCPD size.
  • D. 125 amperes is too small; the calculation yields a higher value.

Feeder OCPD Sizing (Continuous/Noncontinuous)

Overcurrent protective devices for feeders supplying continuous loads must be sized at 125% of the continuous load plus 100% of the noncontinuous load, then rounded up to the next standard OCPD size if necessary.

  • Continuous loads are multiplied by 125%.
  • Noncontinuous loads are multiplied by 100%.
  • Feeder OCPD must be sized to protect the conductors.
  • NEC 215.3 and 240.6(A) apply.

Memory trick: Continuous loads need an extra boost, then pick the next standard fuse.