Journeyman Electrician Exam (NEC)Services, Feeders, and Branch CircuitsMedium

A dwelling unit has a 240V, 8 kW electric range. What is the calculated demand load in amperes for this range, assuming only one range is installed?

  1. A40 amperes
  2. B25 amperes
  3. C33.3 amperes
  4. D30 amperes
Show answer & explanation

Correct answer: C. 33.3 amperes

According to NEC Table 220.55, Column C, for a single household electric range rated 8 kW, the demand factor is 8 kW. The current is calculated as I = P/V = 8000 W / 240 V = 33.33 amperes.

Why the other options are wrong

  • A. 40 amperes is too high; it might be considered an overestimation.
  • B. 25 amperes is too low; it might be mistaken for other appliance calculations.
  • D. 30 amperes is incorrect; the calculation yields a different value.

Electric Range Demand Load

For household electric ranges, the demand load is determined by NEC Table 220.55, which provides a demand factor based on the nameplate rating and number of ranges, then converted to amperes.

  • NEC Table 220.55 is specifically for household electric cooking appliances.
  • For ranges 12 kW or less, Column C is typically used for a single range.
  • Demand load is converted to amperes using I = P/V.

Memory trick: Ranges need a table to shrink their power, then convert to amps.

More Services, Feeders, and Branch Circuits questions