Master Electrician Exam (NEC)General Electrical KnowledgeEasy

A master electrician is installing a new 120V, 15A branch circuit to supply a continuous load. According to NEC Article 210.20(A), what is the maximum continuous load permitted on this circuit?

  1. A15 Amperes
  2. B12 Amperes
  3. C18.75 Amperes
  4. D20 Amperes
Show answer & explanation

Correct answer: B. 12 Amperes

For continuous loads, the branch-circuit overcurrent device rating must not be less than 125% of the continuous load. Conversely, the continuous load must not exceed 80% of the overcurrent device rating. Therefore, 15A * 0.80 = 12A.

Why the other options are wrong

  • A. This is the rating of the overcurrent device, not the maximum continuous load permitted.
  • C. This value (125% of 15A) would be the minimum overcurrent device size if 15A were the continuous load, which is incorrect for this question.
  • D. This is a common next standard overcurrent device size, but not the correct answer for a 15A circuit's continuous load.

Continuous Load

A load where the maximum current is expected to continue for 3 hours or more. NEC requires overcurrent devices for continuous loads to be sized at 125% of the continuous load.

  • Load operates for 3 hours or more.
  • Overcurrent device must be sized at 125% of the continuous load.
  • Continuous load cannot exceed 80% of the overcurrent device rating.

Memory trick: Continuous loads are a '25% more' commitment for protection.