Master Electrician Exam (NEC)General Electrical KnowledgeMedium

A master electrician is installing a new 200A, 208Y/120V service for a commercial building. According to NEC 250.24(C)(1), what is the minimum size required for the grounded (neutral) conductor for this service?

  1. ANo. 4 AWG copper
  2. BNo. 2 AWG copper
  3. CNo. 6 AWG copper
  4. DNo. 1/0 AWG copper
Show answer & explanation

Correct answer: B. No. 2 AWG copper

NEC 250.24(C)(1) requires the grounded conductor to be sized not smaller than specified in Table 250.102(C)(1) and not smaller than the required grounding electrode conductor. For a 200A service, Table 250.102(C)(1) specifies a minimum of No. 2 AWG copper for service conductors up to 200A.

Why the other options are wrong

  • A. This is too small for a 200A service grounded conductor.
  • C. This is too small for a 200A service grounded conductor.
  • D. While larger, this is not the minimum required size and would be oversized.

Service Grounded Conductor Sizing

The grounded (neutral) conductor for a service must be sized to carry the maximum unbalanced current and not be smaller than required by NEC Table 250.102(C)(1) based on the service entrance conductor size.

  • Must carry unbalanced load current.
  • Minimum size determined by NEC Table 250.102(C)(1).
  • Cannot be smaller than required for the grounding electrode conductor.

Memory trick: Neutral needs to be 'Balanced and Bonded' to meet Code.