CSLB C-10 Electrical ContractorWiring Methods and MaterialsMedium

A residential service entrance requires a grounding electrode conductor (GEC) to connect to a concrete-encased electrode (Ufer ground). The service entrance conductors are 4/0 AWG copper. What is the minimum size copper GEC required for this installation, according to NEC Table 250.66?

  1. A1/0 AWG copper
  2. B4 AWG copper
  3. C6 AWG copper
  4. D2 AWG copper
Show answer & explanation

Correct answer: B. 4 AWG copper

According to NEC Table 250.66, for a concrete-encased electrode, the minimum size copper grounding electrode conductor must not be smaller than 4 AWG. This is a specific rule for Ufer grounds regardless of the service conductor size, as long as the service conductors are not extremely large.

Why the other options are wrong

  • A. 1/0 AWG would be significantly oversized and not the minimum required.
  • C. 6 AWG is typically for ground rods or pipe electrodes, not concrete-encased electrodes.
  • D. 2 AWG would be oversized for this application and not the minimum required.

GEC Sizing (Concrete-Encased Electrode)

The sizing of a Grounding Electrode Conductor (GEC) connected to a concrete-encased electrode (Ufer ground) has a specific minimum requirement of 4 AWG copper, irrespective of the service conductor size, as long as the service conductors are not exceptionally large.

  • Refer to NEC Table 250.66
  • Concrete-encased electrodes (Ufer grounds) have specific GEC sizing rules
  • Minimum 4 AWG copper for Ufer ground

Memory trick: Grounding Electrodes: Match the Metal to the Method.

More Wiring Methods and Materials questions