CSLB C-10 Electrical ContractorWiring Methods and MaterialsHard

A three-phase, 480V feeder circuit supplies a 75 kVA continuous load located 150 feet from the panel. The conductors are copper THHN, and the voltage drop must not exceed 3%. What is the minimum required conductor size?

  1. A3/0 AWG
  2. B1 AWG
  3. C2/0 AWG
  4. D1/0 AWG
Show answer & explanation

Correct answer: C. 2/0 AWG

First, calculate the continuous load current. Then, apply the 125% rule for continuous loads. Finally, calculate the maximum allowable voltage drop and use the voltage drop formula to determine the minimum conductor size.

Why the other options are wrong

  • A. Incorrect; while this size meets the voltage drop requirement, it is larger than necessary, leading to increased material costs.
  • B. Incorrect; this size results in a voltage drop exceeding 3%.
  • D. Incorrect; this size results in a voltage drop exceeding 3%.

Three-Phase Voltage Drop Calculation

The process of determining the appropriate conductor size for a three-phase circuit to ensure voltage drop remains within acceptable limits, typically 3% for feeders, considering continuous load adjustments.

  • Voltage drop calculation is critical for efficient and reliable electrical systems.
  • Continuous loads require conductors to be sized at 125% of the load current before applying voltage drop calculations.
  • The three-phase voltage drop formula differs from single-phase, using a √3 multiplier.
  • NEC 215.2(A)(1)(b) recommends a maximum 3% voltage drop for feeders.

Memory trick: Volt Drop: Continuous Current, Then Size Right, Keep It Tight!

More Wiring Methods and Materials questions