CSLB C-10 Electrical ContractorWiring Methods and MaterialsMedium

A residential service entrance requires a grounding electrode conductor (GEC) to connect the service equipment to a ground rod. The service is supplied by 2/0 AWG copper service-entrance conductors. What is the minimum size copper grounding electrode conductor required for this installation, according to NEC Table 250.66?

  1. A4 AWG copper
  2. B2 AWG copper
  3. C8 AWG copper
  4. D6 AWG copper
Show answer & explanation

Correct answer: D. 6 AWG copper

According to NEC Table 250.66, for service-entrance conductors sized 2/0 AWG copper, the minimum size copper grounding electrode conductor (GEC) to a ground rod is 6 AWG copper. This table correlates the GEC size to the size of the largest ungrounded service-entrance conductor.

Why the other options are wrong

  • A. 4 AWG copper is larger than required for this application.
  • B. 2 AWG copper is significantly larger than required for this application.
  • C. 8 AWG copper is too small for 2/0 AWG service-entrance conductors.

GEC Sizing (Table 250.66)

NEC Table 250.66 specifies the minimum size of the grounding electrode conductor (GEC) based on the size of the largest ungrounded service-entrance conductor or equivalent area for parallel conductors.

  • The GEC protects the electrical system from overvoltages and lightning.
  • Different GEC sizes are required for connection to different types of grounding electrodes (e.g., ground rod, concrete-encased electrode, water pipe).
  • The table provides separate columns for copper and aluminum/copper-clad aluminum GECs.

Memory trick: GEC size, for grounding's might, Table 250.66, sets it right!