Journeyman Electrician Exam (NEC)Equipment and DevicesHard

A journeyman electrician is installing a 300-ampere, 208Y/120-volt service for a commercial building. The service conductors are 3/0 AWG copper with THHN insulation. What is the minimum size grounding electrode conductor (GEC) required if the service entrance conductors are not paralleled?

  1. ANo. 1/0 AWG copper
  2. BNo. 2 AWG copper
  3. CNo. 2/0 AWG copper
  4. DNo. 4 AWG copper
Show answer & explanation

Correct answer: B. No. 2 AWG copper

According to NEC Table 250.66, the size of the grounding electrode conductor is based on the size of the largest ungrounded service-entrance conductor. For 3/0 AWG copper service conductors, the minimum size copper grounding electrode conductor is No. 2 AWG.

Why the other options are wrong

  • A. No. 1/0 AWG copper is for 4/0 AWG or 250 kcmil service conductors.
  • C. No. 2/0 AWG copper is for 350 kcmil or 400 kcmil service conductors.
  • D. No. 4 AWG copper is for 1/0 AWG or 2/0 AWG service conductors, or smaller.

Grounding Electrode Conductor Sizing

Determining the minimum size of the grounding electrode conductor (GEC) based on the size of the largest ungrounded service-entrance conductor or equivalent area for paralleled conductors, as specified in NEC Table 250.66.

  • Connects the grounding electrode to the service equipment enclosure.
  • Size is dependent on the service conductor size, not the service overcurrent protection.
  • NEC Table 250.66 is the primary reference.

Memory trick: Service wire size is key, GEC follows its decree!