Commercial Building Inspector B2Wall Construction and Wall CoveringsHard

A client is proposing a new commercial building with a 2-hour fire-resistance-rated masonry wall. The wall will be constructed using 8-inch (203 mm) concrete masonry units (CMU). What is the minimum equivalent thickness of solid masonry required for this wall assembly to achieve the 2-hour rating, assuming standard weight concrete masonry?

  1. A3.6 inches (91 mm)
  2. B5.3 inches (135 mm)
  3. C4.8 inches (122 mm)
  4. D4.0 inches (102 mm)
Show answer & explanation

Correct answer: C. 4.8 inches (122 mm)

According to IBC Table 722.3.2.2(1) for concrete masonry walls, a 2-hour fire-resistance rating requires a minimum equivalent thickness of 4.8 inches (122 mm) for standard weight concrete masonry (120 pcf). The nominal 8-inch CMU must achieve this equivalent solid thickness.

Why the other options are wrong

  • A. 3.6 inches is for a 1.5-hour rating, not 2 hours.
  • B. 5.3 inches is for a 3-hour rating, not 2 hours.
  • D. 4.0 inches is for a 1.5-hour rating or specific lightweight units, not standard weight 2-hour.

CMU Fire-Resistance Equivalent Thickness

The minimum equivalent solid thickness of concrete masonry units required to achieve a specific fire-resistance rating.

  • Equivalent thickness accounts for the hollow spaces in CMU.
  • Fire-resistance rating depends on concrete type (e.g., normal weight, lightweight) and aggregate.
  • IBC Table 722.3.2.2(1) provides these values.

Memory trick: CMU's fire strength: thickness, weight, and the clock's tick.