EPA Section 608 Universal Certification ExamType III (Low-Pressure Appliances)Easy

A technician is performing a leak test on a low-pressure chiller using soap bubbles. At what pressure should the system typically be pressurized for this type of test?

  1. ABelow 0 psig (in a vacuum)
  2. BAt the system's normal operating discharge pressure
  3. CBetween 0 and 10 psig
  4. DAbove 30 psig
Show answer & explanation

Correct answer: C. Between 0 and 10 psig

Low-pressure chillers should be pressurized between 0 and 10 psig for leak testing. Pressurizing above 10 psig can cause the rupture disc to fail, leading to refrigerant release.

Why the other options are wrong

  • A. A vacuum cannot be used for a soap bubble leak test, as it requires positive pressure.
  • B. Normal operating discharge pressure is typically much higher and would exceed the safe leak test pressure for low-pressure systems.
  • D. Pressurizing above 10 psig could rupture the low-pressure chiller's rupture disc.

Low-Pressure Leak Test Pressure

For low-pressure chillers, leak tests using positive pressure (like nitrogen) should be conducted between 0 and 10 psig to prevent damage to the system's rupture disc.

  • 0-10 psig is the safe range for positive pressure leak tests.
  • Exceeding 10 psig risks rupturing the disc.
  • Often uses nitrogen for pressurization.

Memory trick: Don't 'POP' the chiller with too much pressure, keep it low and slow.