EPA Section 608 Universal Certification ExamType III (Low-Pressure Appliances)Medium

A technician is decommissioning a low-pressure chiller that contains 150 lbs of R-11. The EPA-mandated recovery level for this appliance, considering its charge size, is:

  1. A25 inches of Hg vacuum.
  2. B20 inches of Hg vacuum.
  3. C10 inches of Hg vacuum.
  4. D15 inches of Hg vacuum.
Show answer & explanation

Correct answer: A. 25 inches of Hg vacuum.

For low-pressure appliances with a charge of 50 lbs or more, the EPA requires evacuation to 25 inches of Hg vacuum. This ensures a substantial amount of refrigerant is recovered, reducing environmental impact.

Why the other options are wrong

  • B. 20 inches of Hg vacuum is not a standard EPA recovery level for low-pressure appliances.
  • C. 10 inches of Hg vacuum is for appliances with less than 50 lbs charge, and manufactured before 1993.
  • D. 15 inches of Hg vacuum is for appliances with less than 50 lbs charge, manufactured in or after 1993.

Low-Pressure Recovery Standard (>=50 lbs)

The EPA-mandated vacuum level for recovering refrigerant from low-pressure appliances with a charge of 50 lbs or more.

  • Applies to low-pressure systems (Type III).
  • For systems with 50 lbs or more of refrigerant.
  • Requires recovery to 25 inches of Hg vacuum.

Memory trick: Fifty pounds or more, twenty-five is the score!