A journeyman is installing a new 400-ampere, 120/208-volt service for a commercial tenant. The service-entrance conductors are 500 kcmil copper. The main bonding jumper is made of copper. What is the minimum size copper main bonding jumper required for this service, according to NEC® 250.102(C)(1)?

  1. A2/0 AWG
  2. B3/0 AWG
  3. C300 kcmil
  4. D250 kcmil
Show answer & explanation

Correct answer: D. 250 kcmil

According to NEC® Table 250.102(C)(1), for ungrounded service-entrance conductors with a size of 500 kcmil copper, the minimum size copper main bonding jumper required is 250 kcmil.

Why the other options are wrong

  • A. 2/0 AWG is for service conductors up to 400 kcmil.
  • B. 3/0 AWG is for service conductors up to 500 kcmil in some older tables or for specific applications, but not for MBJ with 500 kcmil service conductors.
  • C. 300 kcmil is larger than the minimum required for 500 kcmil service conductors.

Main Bonding Jumper Sizing (NEC® 250.102(C)(1))

The main bonding jumper (MBJ) connects the equipment grounding conductor to the grounded service conductor and service enclosure. Its minimum size is determined by the largest ungrounded service-entrance conductors, using NEC® Table 250.102(C)(1).

  • Connects ground and neutral at the service.
  • Size derived from the largest ungrounded service-entrance conductors.
  • Reference NEC® Table 250.102(C)(1).

Memory trick: MBJ's size mirrors the biggest service wire's might.