Journeyman Electrician Exam (NEC)Grounding and BondingEasy

An electrician is designing the grounding system for a new service where a metal underground water pipe is available as a grounding electrode. What is the minimum length of contact with the earth required for this water pipe to qualify as a grounding electrode, according to NEC® 250.52(A)(1)?

  1. A15 ft (4.5 m)
  2. B10 ft (3.0 m)
  3. C5 ft (1.5 m)
  4. D20 ft (6.0 m)
Show answer & explanation

Correct answer: B. 10 ft (3.0 m)

NEC® 250.52(A)(1) specifies that a metal underground water pipe must be in direct contact with the earth for 10 ft (3.0 m) or more to qualify as a grounding electrode.

Why the other options are wrong

  • A. 15 ft is more than the minimum required but not the minimum itself.
  • C. 5 ft is insufficient for a metal underground water pipe to qualify as a grounding electrode.
  • D. 20 ft is more than the minimum required but not the minimum itself; it is the minimum length for a ground ring or concrete-encased electrode.

Metal Water Pipe Electrode Length

For a metal underground water pipe to be considered an effective grounding electrode, it must have at least 10 ft (3.0 m) of direct contact with the earth, as specified in NEC® 250.52(A)(1).

  • Applies specifically to metal underground water pipes.
  • Minimum 10 ft (3.0 m) of direct earth contact.
  • Must be supplemented by an additional electrode (NEC® 250.53(D)(2)).

Memory trick: Water pipe needs a 'ten-foot dive' to be a good ground.