Journeyman Electrician Exam (NEC)Grounding and BondingHard

A journeyman is inspecting the grounding system of a new commercial service. The building has a metal frame, and the service-entrance conductors are 750 kcmil copper. The grounding electrode conductor is connected to the building's metal frame. What is the minimum size of the GEC to the metal frame?

  1. A4/0 AWG copper
  2. B250 kcmil copper
  3. C2/0 AWG copper
  4. D3/0 AWG copper
Show answer & explanation

Correct answer: B. 250 kcmil copper

According to NEC Table 250.66, for service-entrance conductors of 750 kcmil copper, the minimum size grounding electrode conductor is 250 kcmil copper. The building steel is considered a grounding electrode and its GEC is sized based on the service conductors.

Why the other options are wrong

  • A. This size is too small for 750 kcmil service conductors.
  • C. This size is too small for 750 kcmil service conductors.
  • D. This size is too small for 750 kcmil service conductors.

GEC Sizing to Building Steel

When a building's metal frame is used as a grounding electrode, the grounding electrode conductor (GEC) is sized according to NEC Table 250.66, based on the size of the service-entrance conductors.

  • Building steel is a common type of grounding electrode.
  • GEC size determined by NEC Table 250.66.
  • Based on the largest ungrounded service-entrance conductor size.

Memory trick: Steel Frame GEC: Service size dictates the gain!