CSLB C-36 Plumbing ContractorFixture and Appliance InstallationHard

A plumber is performing a routine inspection of a commercial building's backflow prevention assembly, which is an RP (Reduced Pressure) assembly. During the test, the plumber observes that the differential pressure relief valve opens when the pressure drop across the No. 1 check valve is less than 2 psi. According to typical testing standards (e.g., ASSE 5000 series), what does this indicate?

  1. AThe No. 1 check valve is fouled.
  2. BThe No. 2 check valve is leaking.
  3. CThe upstream shut-off valve is leaking.
  4. DThe differential pressure relief valve is failing to hold pressure.
Show answer & explanation

Correct answer: D. The differential pressure relief valve is failing to hold pressure.

For an RP assembly, the relief valve is designed to open when the differential pressure across the No. 1 check valve drops to a specific minimum (typically 2 psi or less, depending on the manufacturer and specific standard). If it opens when the pressure drop is *less than* the required minimum (e.g., it opens at 1 psi when it should hold at 2 psi), it indicates that the relief valve itself is faulty and is not holding the required differential pressure, which could lead to backflow if the No. 1 check valve also fails.

Why the other options are wrong

  • A. A fouled No. 1 check valve would typically cause a *higher* pressure drop across it, or a complete failure to hold pressure, not necessarily cause the relief valve to open at too low a differential.
  • B. A leaking No. 2 check valve would typically cause the pressure in the zone between the check valves to build up, potentially causing the relief valve to open, but the issue described focuses on the *opening threshold* of the relief valve itself.
  • C. A leaking upstream shut-off valve would not directly cause the relief valve to open prematurely at a low differential pressure; it would affect the overall system pressure or flow.

RP Backflow Assembly Failure (Relief Valve)

A malfunction in a Reduced Pressure (RP) backflow prevention assembly where the differential pressure relief valve opens at a pressure differential lower than its design specification, indicating a failure to hold adequate pressure.

  • Relief valve must hold a minimum differential pressure (e.g., 2 psi or more) above the supply pressure.
  • Opening below this threshold signals a faulty relief valve.
  • Compromises the safety of the RP assembly's backflow protection.

Memory trick: If the relief valve dips below the 2 psi trip, your protection's slip.