CSLB C-46 Solar ContractorPhotovoltaic System InstallationHard

A solar technician is performing a final inspection of a roof-mounted PV array before commissioning. They notice that the grounding conductor from the PV array frame is connected directly to a copper cold-water pipe on the roof. What is the primary concern with this grounding method?

  1. AThe connection point is exposed to weather and will corrode.
  2. BIt violates NEC requirements for rapid shutdown of PV systems.
  3. CThe cold-water pipe is not a suitable equipment grounding conductor.
  4. DThe pipe may not have a continuous metallic path back to the service entrance.
Show answer & explanation

Correct answer: D. The pipe may not have a continuous metallic path back to the service entrance.

While a cold-water pipe can sometimes be part of a grounding electrode system, connecting directly to it on the roof has a primary concern: its metallic continuity back to the service entrance grounding electrode conductor is often unreliable. Sections of the pipe could be non-metallic (e.g., PEX), or metallic pipe could be interrupted by non-conductive fittings (e.g., dielectric unions, plastic valves). NEC requires a continuous, reliable metallic path for equipment grounding, which a utility water pipe cannot guarantee without verification. It is not an approved grounding electrode for a PV system's equipment grounding conductor.

Why the other options are wrong

  • A. Corrosion is a concern for any outdoor connection, but the primary issue is the *reliability* of the grounding path itself.
  • B. This grounding method is unrelated to rapid shutdown requirements, which address DC conductors and array voltage during emergencies.
  • C. A cold-water pipe *can* be part of a grounding electrode system if it meets specific NEC requirements, but it's not a suitable *equipment grounding conductor* for the PV array without a verified continuous metallic path.

PV Equipment Grounding Reliability

Ensuring a continuous, low-impedance metallic path from all non-current-carrying metal parts of the PV system back to the main service grounding electrode system.

  • Prevents electric shock hazards by safely clearing ground faults.
  • Requires dedicated equipment grounding conductors or approved metallic raceways/racking.
  • Utility water pipes are generally not reliable for equipment grounding due to potential interruptions.

Memory trick: Grounding must be sound and true, a continuous path for safety too!