CSLB C-46 Solar ContractorPhotovoltaic System InstallationMedium

A solar installer is connecting a grid-tied PV system to a residential service panel. The system includes a string inverter with a maximum AC output current of 30A. The existing main service panel has a 200A busbar. According to NEC 705.12(B)(2), what is the maximum overcurrent protection device (OCPD) rating allowed for the PV inverter's AC output circuit if the main breaker is 200A?

  1. A30A
  2. B50A
  3. C40A
  4. D60A
Show answer & explanation

Correct answer: C. 40A

NEC 705.12(B)(2) states that the sum of the ampere ratings of all overcurrent devices supplying power to a busbar cannot exceed 120% of the busbar's ampere rating. This is often referred to as the 120% rule. The formula is: (Busbar Rating * 1.2) - Main Breaker Rating = Max PV OCPD. So, (200A * 1.2) - 200A = 240A - 200A = 40A. The maximum OCPD for the PV inverter output is 40A.

Why the other options are wrong

  • A. 30A is the inverter output current, not the maximum OCPD allowed by code.
  • B. 50A exceeds the calculated maximum OCPD allowed by the 120% rule.
  • D. 60A significantly exceeds the calculated maximum OCPD allowed by the 120% rule.

NEC 705.12(B)(2) (120% Rule for Busbar)

Limits the total current that can be supplied to a busbar by both the utility and PV system to 120% of the busbar's rating.

  • Ensures the busbar is not overloaded by combined utility and PV current.
  • Formula: (Busbar Rating * 1.2) - Main Breaker Rating = Max PV OCPD.
  • Critical for safe interconnection of PV systems to existing electrical panels.

Memory trick: Busbar's 120% limit, keep the total current fit!