A solar installer is connecting a new grid-tied string inverter to a residential service panel. The inverter has a maximum continuous output current of 28A at 240V. According to NEC 690.8(A)(1), what is the minimum required ampacity for the conductors connecting the inverter to the overcurrent protection device (OCPD)?

  1. A40A
  2. B35A
  3. C50A
  4. D28A
Show answer & explanation

Correct answer: B. 35A

NEC 690.8(A)(1) requires that PV system circuit conductors be sized to carry a minimum of 125% of the maximum continuous current. For a 28A continuous current, the minimum ampacity is 28A * 1.25 = 35A.

Why the other options are wrong

  • A. This value is higher than required by the 125% rule, potentially leading to unnecessary cost or oversized conductors.
  • C. This value is significantly higher than required by the 125% rule, indicating a misapplication of the NEC.
  • D. This is the continuous current, not the minimum required ampacity after applying the 125% multiplier.

NEC 690.8(A)(1) Conductor Sizing

NEC 690.8(A)(1) mandates that PV system circuit conductors must be sized to carry a minimum of 125% of the maximum continuous current to account for potential sustained loads.

  • Applies to PV system circuit conductors (DC and AC).
  • Calculated as 125% of the maximum continuous current.
  • Ensures conductors can handle sustained operational currents without overheating.

Memory trick: Always Multiply Current by 1.25 for PV Conductors.