CSLB General Building (B)Finishes and Building EnvelopeMedium

A contractor is sizing attic ventilation for a single-story home with a gable roof and no vapor retarder installed at the ceiling. The attic floor area is 1,800 square feet. Per the 1/150 rule with ventilation split evenly between high (ridge) and low (soffit) vents, how much net free ventilating area is required at the soffit vents alone?

  1. A1,728 square inches
  2. B1,200 square inches
  3. C432 square inches
  4. D864 square inches
Show answer & explanation

Correct answer: D. 864 square inches

Total required net free area = 1,800 sq ft ÷ 150 = 12 sq ft = 1,728 sq in. Since ventilation must be split 50/50 between upper (ridge) and lower (soffit) vents, the soffit portion is 1,728 ÷ 2 = 864 sq in.

Why the other options are wrong

  • A. This is the total required net free area, not the soffit-only portion.
  • B. This value does not correspond to any correct division of the total.
  • C. This is one-quarter of the total, not half.

1/150 Attic Ventilation Rule

Attics without a vapor retarder require net free ventilation area equal to 1/150 of the attic floor area, split between upper and lower vents.

  • 1/300 ratio allowed if 50% of vents are high, 50% low, plus vapor retarder or specific conditions
  • Convert square feet to square inches: 1 sq ft = 144 sq in
  • Ventilation must balance intake (soffit) and exhaust (ridge)

Memory trick: One-fiftieth for balance, half goes up, half goes down.

More Finishes and Building Envelope questions