CSLB C-20 HVAC ContractorVentilation and Air DistributionHard

Per ASHRAE 62.2 whole-house mechanical ventilation requirements, a home has 1,800 square feet of conditioned floor area and 3 bedrooms. What is the minimum required continuous whole-house ventilation rate?

  1. A84 CFM
  2. B54 CFM
  3. C90 CFM
  4. D60 CFM
Show answer & explanation

Correct answer: A. 84 CFM

ASHRAE 62.2 formula: CFM = 0.03 × floor area + 7.5 × (bedrooms + 1) = 0.03 × 1,800 + 7.5 × (3+1) = 54 + 30 = 84 CFM continuous whole-house ventilation.

Why the other options are wrong

  • B. This is only the floor-area component, omitting the bedroom factor.
  • C. This slightly overstates the result from a rounding or formula error.
  • D. This value doesn't match either component of the formula.

ASHRAE 62.2 Whole-House Ventilation

A formula-based standard requiring continuous mechanical ventilation calculated from floor area and number of bedrooms to maintain indoor air quality.

  • Formula: CFM = 0.03×floor area + 7.5×(bedrooms+1)
  • Applies to whole-house continuous ventilation systems
  • Adopted by reference in Title 24 residential IAQ requirements

Memory trick: Point-oh-three times area, plus seven-point-five per body.