CSLB C-20 HVAC ContractorControls, Electrical and SafetyMedium

A technician uses a megohmmeter to test the insulation resistance of a compressor motor winding to ground and reads 0.3 megohms. According to common industry standards, what does this reading indicate?

  1. AThe motor is properly grounded and safe to energize
  2. BThe winding insulation is in acceptable condition for continued service
  3. CThe reading indicates a normal capacitor discharge value
  4. DThe motor should be shut down; insulation has degraded and poses a ground-fault/shock hazard
Show answer & explanation

Correct answer: D. The motor should be shut down; insulation has degraded and poses a ground-fault/shock hazard

Industry standards generally consider insulation resistance readings below 1 megohm (often 2 megohms minimum for larger motors) unacceptable, indicating degraded winding insulation that could allow current to leak to the motor casing, creating a shock or ground-fault hazard. A 0.3 megohm reading is well below this threshold and calls for motor replacement or rewinding.

Why the other options are wrong

  • A. A low insulation resistance reading indicates a potential fault path to ground, not proper grounding.
  • B. 0.3 megohm is far below the accepted minimum (typically 1-2 megohms), so it is not acceptable.
  • C. Megohmmeter readings measure insulation resistance, not capacitor discharge values.

Megohmmeter Insulation Test

A megohmmeter (megger) measures insulation resistance between motor windings and ground; readings below 1 megohm typically indicate insulation breakdown and unsafe operating conditions.

  • Minimum acceptable: usually 1-2 megohms depending on motor size/voltage
  • Low readings indicate moisture intrusion or winding insulation failure
  • Test performed with motor de-energized and disconnected

Memory trick: Low megohms = leaky insulation = 'mega' problem.