CSLB C-10 Electrical ContractorWiring Methods and MaterialsMedium

A technician drives a single 8-foot ground rod at a residence and measures 32 ohms of resistance to earth using a ground resistance tester. Per NEC 250.53(A)(2), what must the technician do?

  1. AIncrease the size of the grounding electrode conductor to compensate
  2. BInstall a supplemental grounding electrode bonded to the first rod
  3. CReplace the rod with one at least 12 feet long
  4. DNothing further, as 32 ohms is within the acceptable range
Show answer & explanation

Correct answer: B. Install a supplemental grounding electrode bonded to the first rod

NEC 250.53(A)(2) requires that a single rod, pipe, or plate electrode with a resistance to earth exceeding 25 ohms be supplemented by an additional electrode. Since 32 ohms exceeds this threshold, a second electrode must be installed and bonded to the first.

Why the other options are wrong

  • A. GEC sizing is unrelated to correcting excessive ground resistance readings.
  • C. Rod length alone does not satisfy the code requirement; a second electrode is mandated instead.
  • D. 32 ohms exceeds the 25-ohm threshold, so additional action is required.

Single Ground Rod 25-Ohm Rule

NEC 250.53(A)(2) requires a single rod, pipe, or plate electrode exceeding 25 ohms resistance to be supplemented with an additional electrode.

  • 25 ohms is the threshold for single-rod electrodes.
  • If exceeded, one supplemental electrode is required (no further testing needed once added).
  • Supplemental electrode must be bonded to the first.

Memory trick: 'Twenty-five or add a friend' — over 25 ohms needs a second rod.