CSLB C-10 Electrical ContractorWiring Methods and MaterialsMedium

A metal wireway has an interior cross-sectional area of 12 square inches. Per NEC 376.22(A), conductors may occupy no more than 20% of this area. What is the maximum allowable conductor fill area?

  1. A1.2 in²
  2. B4.8 in²
  3. C2.4 in²
  4. D3.6 in²
Show answer & explanation

Correct answer: C. 2.4 in²

The 20% fill rule for wireways is calculated as 12 in² × 0.20 = 2.4 in². This limit ensures adequate heat dissipation and ease of conductor installation within the wireway.

Why the other options are wrong

  • A. This reflects a 10% fill, not the 20% rule.
  • B. This reflects a 40% fill, far exceeding the wireway fill limit.
  • D. This reflects a 30% fill, exceeding the allowed limit.

Wireway Fill (376.22)

Conductors in a metal wireway may not exceed 20% of the wireway's interior cross-sectional area.

  • 20% max fill for general conductor fill
  • Multiply total area by 0.20 to find max fill
  • Additional derating applies if more than 30 current-carrying conductors are present

Memory trick: One-fifth full keeps the wireway cool.