Commercial Building Inspector B2General Administration, Permits, and PlansHard

A commercial building inspector is reviewing plans for a new 10-story Group R-2 apartment building. The building is designed as Type I-A construction. What is the minimum fire-resistance rating required for the floor construction, including the supporting beams and girders, below the first story?

  1. A3 hours
  2. B4 hours
  3. C1 hour
  4. D2 hours
Show answer & explanation

Correct answer: A. 3 hours

For Type I-A construction, IBC Table 601 specifies a minimum 3-hour fire-resistance rating for the floor construction, including supporting beams and girders, below the first story. This high rating is crucial for the most fire-resistive construction type.

Why the other options are wrong

  • B. 4 hours is typically reserved for fire walls or specific elements in very high hazard occupancies, not standard floor construction.
  • C. 1 hour is typically for less protected types or specific non-bearing elements.
  • D. 2 hours is common for floor construction in Type I-B or II-A, but not Type I-A below the first story.

Type I-A Floor Construction Rating

In Type I-A construction, the most fire-resistive type, floor construction and its supports (including below the first story) must have a minimum 3-hour fire-resistance rating.

  • Type I-A uses noncombustible materials.
  • Highest level of fire protection.
  • Specific ratings for various structural elements.

Memory trick: Super-strong Type 1-A floors below ground always need three hours of fire protection.